Figure 57 Binding cables where they must be bent
Route, bind, and attach excess cables for easy, safe maintenance activities and correct operations.
Do not tie power cables to slide rails.
When you connect a cable to an articulated part, for example, when you connect a grounding
cable to a cabinet door, leave enough slack in cables and make sure they are not stressed from
any movement of the part.
Cables must be protected at points where they might rub or come in contact with sharp edges or
heated areas. Use high temperature cables near heat sources.
Securely fasten cables and take adequate measures to prevent loose connections.
Figure 58 Securely fastening cables
(1) Flat washer (2) Spring washer (3) Nut
Fasten heavy or rigid power cables at the connectors to relief stress.
Do not use tapping screws to fasten the connecting terminals.
Bind together cables that are the same type and routed in the same direction.
Table 37 lists
the cable bundling specifications.
Table 37 Tie-binding parameters
Cable bundle diameter (mm)
S
p
ace between bundles (mm)
10 80 to 150
10 to 30 150 to 200
(1)
(1)(2) (3)
(1)
(1)(2) (3)